Distributed Energy Resources, IEEE 13-bus grid, IEEE 1547-2018, time-based ride-through, voltage ride-through

Access Setting

Masters Thesis-Open Access

Abstract

Distributed Energy Resources (DERs) include inverter-based power generation units, which are increasing in demand due to the rising consumption of energy, need for improved grid stability, and other environmental factors. DERs can either supply or supplement the grid using different control strategies depending on the grid’s needs. IEEE standard 1547-2018 dictates the interconnection and operation requirements of grid-connected DERs under nominal and abnormal voltage conditions. Although inverter ride-through operation has been widely studied, the effects of the standard’s time-based requirements within a distribution grid system require further investigation.

This study investigates how the IEEE 1547-2018 time-based ride-through requirements affect a DER-supplied distribution system. The analysis is performed using the well-known IEEE 13-bus feeder, with a wind farm included as supplementary energy source. The inverter’s control is analyzed in terms of its ability to provide suitable voltage-reactive power support during faults while keeping the grid stable. This study is performed in real time using a Real Time Digital Simulator (RTDS) and its proprietary software, RSCAD.

The results are used to evaluate the capabilities of the IEEE 1547-2018 standard, with particular focus on the time-based voltage ride-through control, and to analyze the effect of the standard on the overall grid operation. The investigation compares system behavior with and without the DER under different voltage disturbances, allowing the standard’s voltage ride-through strategy to be evaluated. The results indicate that the time-based ride-through control scheme balances the need to protect DER power electronics during abnormal voltage conditions with the need to maintain DER availability for distribution system support.